1114B.2.1
[For SFM] General.
- In buildings or portions of buildings required to be accessible, accessible means of
egress shall be provided in the same number as required for exits by Chapter 10.
- When an exit required by Chapter 10 is not accessible, an area for evacuation assistance
shall be provided.
Areas for evacuation assistance shall comply with the requirements of this code and
shall adjoin an accessible route of travel complying with this code.
EXCEPTIONS: 1. Areas of evacuation assistance are not required in buildings or
facilities having a supervised automatic sprinkler system.
2. In alterations of existing buildings, areas of evacuation assistance are not
required.
1114B.2.2 [For SFM] Areas for evacuation assistance.
1114B.2.2.1 [For SFM] Location and construction.
An area for evacuation assistance shall be one of the following:
1. [For SFM] A portion of a stairway landing within a smokeproof enclosure, complying
with Section 1005.3.3.
2. [For SFM] A portion of an exterior exit balcony located immediately adjacent to an
exit stairway when the exterior exit balcony complies with Section 1006.3. Openings to the
exterior of the building located within 20 feet (6096 mm) of the area for evacuation
assistance shall be protected with fire assemblies having a three-fourths-hour
fire-protection rating.
3. [For SFM] A portion of a one-hour fire-resistive corridor complying with Section
1004.3.4 located immediately adjacent to an exit enclosure.
4. [For SFM] A vestibule located immediately adjacent to an exit enclosure and
constructed to the same fire-resistive standards as required by Section 1004.3.4.
5. [For SFM] A portion of a stairway landing within an exit enclosure which is vented
to the exterior and is separated from the interior of the building by not less than
one-hour fire-resistive door assemblies.
6. [For SFM] When approved by the building official, an area or room which is separated
from other portions of the building by a smoke barrier. Smoke barriers shall have a
fire-resistive rating of not less than one hour and shall completely enclose the area or
room. Doors in the smoke barrier shall be tightfitting smoke- and draft-control assemblies
having a fire-protection rating of not less than 20 minutes and shall be self-closing or
automatic closing.
The area or room shall be provided with an exit directly to an exit enclosure. When the
room or area exits into an exit enclosure which is required to be of more than one-hour
fire-resistive construction, the room or area shall have the same fire-resistive
construction, including the same opening protection, as required for the adjacent exit
enclosure.
7. [For SFM] An elevator lobby complying with Section 1114B.2.3.
1114B.2.2.2 [For SFM] Size. Each area for
evacuation assistance shall provide at least two accessible areas that are not less than
30 inches by 48 inches (762 mm by 1219 mm). The area for evacuation assistance shall not
encroach on any required exit width. The total number of such 30-inch by 48-inch (762 mm
by 1219 mm) areas per story shall not be less than one for every 200 persons of calculated
occupant load served by the area for evacuation assistance.
EXCEPTION: The building official may reduce the minimum number of 30-inch by
48-inch (762 mm by 1219 mm) areas to one for each area for evacuation assistance on floors
where the occupant load is less than 200.
1114B.2.2.3 [For SFM] Adjacent stairway width.
Each stairway adjacent to an area for evacuation assistance shall have a minimum clear
width of 48 inches (1219 mm) between handrails.
1114B.2.2.4 [For SFM] Two-way communication.
1114B.2.2.4.1 [For SFM] A telephone with controlled access to a public telephone system
or another method of two-way communication shall be provided between each area of refuge
and the primary entry. The fire department may approve a location other than the primary
entry.
1114B.2.2.4.2 [For DSA/AC] A method of two-way communication with both visible and
audible communication shall be provided between each area of evacuation assistance and the
primary entry. A button in the area of rescue assistance shall activate both a light in
the area of rescue assistance indicating that rescue has been requested and a light at the
primary entry indicating that rescue is being requested. A button at the primary entry
shall activate both a light at the primary entry and a light in the area of rescue
assistance indicating that the request has been received.
A telephone with controlled access to a public telephone system or another method of
two-way communication shall be provided between each area of refuge and the primary entry.
The fire department may approve a location other than the primary entry.
1114B.2.2.5 [For SFM] Identification.
Each area for evacuation assistance shall be identified by a sign which states AREA FOR
EVACUATION ASSISTANCE and the international symbol of accessibility. The sign shall be
illuminated when exit sign illumination is required. In each area for evacuation
assistance, instructions on the use of the area under emergency conditions shall be posted
adjoining the two-way communication system.
1114B.2.3 [For SFM] Area for evacuation assistance, high-
rise alternative. Within a building of any height or occupancy constructed
in accordance with the requirements of Sections 403.1 through 403.10, an area for
evacuation assistance may be located in the elevator lobby when:
1. The area for evacuation assistance complies with the requirements for size, two-way
communication and identification as specified in Section 1114B.2.2; and
2. Elevator shafts and adjacent lobbies are pressurized as required for smoke-proof
enclosures in Section 1005.3.3. Such pressurization system shall be activated by smoke
detectors on each floor located in a manner approved by the building official.
Pressurization equipment and its ductwork within the building shall be separated from
other portions of the building by a minimum two- hour fire-resistive construction.
1114B.2.4 [For SFM] Alarms/emergency warning
systems/accessibility. If emergency warning systems are required, they
shall activate a means of warning the hearing impaired. Emergency warning systems as part
of the fire-alarm system shall be designed and installed in accordance with NFPA 72 as
amended in Chapter 35.