1114B FACILITY ACCESSIBILITY

When buildings are required to be accessible, buildings and facilities shall be
accessible as provided in this section and in those sections listed in
Section 1114B.1.1
.

Design & construction, general Accessible route of travel Primary entry access
Signs Adaptable dwelling units Egress and areas for Evacuation Assistance


*For residential apartments,
see section 1109A



 

 

 

 

 

 

 

 

 

top

 

 

 

 

 

 


1114B.1 Design and Construction.

1114B.1.1 General. When accessibility is required by this chapter, it shall be designed and constructed to meet the minimum requirements of the following sections:

See also Part 3, California Electrical Code, and Part 5, California Plumbing Code.



top














1114B.1.2 Accessible route of travel.

When a building, or portion of a building, is required to be accessible or adaptable, an accessible route of travel shall be provided:

  • To all portions of the building,
  • To accessible building entrances, and
  • Between the building and the public way.
  • Except within an individual dwelling unit, an accessible route of travel shall not pass through kitchens, storage rooms, restrooms, closets or other spaces used for similar purposes.
  • At least one accessible route within the boundary of the site shall be provided from public transportation stops, accessible parking and accessible passenger loading zones, and public streets or sidewalks, to the accessible building entrance they serve.
  • The accessible route shall, to the maximum extent feasible, coincide with the route for the general public.
  • At least one accessible route shall connect accessible buildings, facilities, elements and spaces that are on the same site.
  • At least one accessible route shall connect accessible building or facility entrances with all accessible spaces and elements and with all accessible dwelling units within the building or facility.
  • An accessible route shall connect at least one accessible entrance of each accessible dwelling unit with those exterior and interior spaces and facilities that serve the accessible dwelling unit.

Where more than one route of travel is provided, all routes shall be accessible.

EXCEPTION: Where an elevator is provided for vertical access, only one elevator is required. Where more than one elevator is provided, all elevators shall be accessible.

See Section 1114B.1.1 for a list of code sections applicable to accessible route of travel.

 

top






1114B.1.3 Primary entry access. All entrances and all exterior ground-level exits shall be accessible in compliance with Section 1133B.1.1.


top






1114B.1.4 Signs. See Section 1117B.5.





top




1114B.1.5 Adaptable dwelling units. See Section 1111B.

 

top






 

 

 



1114B.2 Egress and Areas for Evacuation Assistance

1114B.2.1 [For SFM] General.

  • In buildings or portions of buildings required to be accessible, accessible means of egress shall be provided in the same number as required for exits by Chapter 10.
  • When an exit required by Chapter 10 is not accessible, an area for evacuation assistance shall be provided.

Areas for evacuation assistance shall comply with the requirements of this code and shall adjoin an accessible route of travel complying with this code.

EXCEPTIONS: 1. Areas of evacuation assistance are not required in buildings or facilities having a supervised automatic sprinkler system.

2. In alterations of existing buildings, areas of evacuation assistance are not required.


1114B.2.2 [For SFM] Areas for evacuation assistance.

1114B.2.2.1 [For SFM] Location and construction. An area for evacuation assistance shall be one of the following:

1. [For SFM] A portion of a stairway landing within a smokeproof enclosure, complying with Section 1005.3.3.

2. [For SFM] A portion of an exterior exit balcony located immediately adjacent to an exit stairway when the exterior exit balcony complies with Section 1006.3. Openings to the exterior of the building located within 20 feet (6096 mm) of the area for evacuation assistance shall be protected with fire assemblies having a three-fourths-hour fire-protection rating.

3. [For SFM] A portion of a one-hour fire-resistive corridor complying with Section 1004.3.4 located immediately adjacent to an exit enclosure.

4. [For SFM] A vestibule located immediately adjacent to an exit enclosure and constructed to the same fire-resistive standards as required by Section 1004.3.4.

5. [For SFM] A portion of a stairway landing within an exit enclosure which is vented to the exterior and is separated from the interior of the building by not less than one-hour fire-resistive door assemblies.

6. [For SFM] When approved by the building official, an area or room which is separated from other portions of the building by a smoke barrier. Smoke barriers shall have a fire-resistive rating of not less than one hour and shall completely enclose the area or room. Doors in the smoke barrier shall be tightfitting smoke- and draft-control assemblies having a fire-protection rating of not less than 20 minutes and shall be self-closing or automatic closing.

The area or room shall be provided with an exit directly to an exit enclosure. When the room or area exits into an exit enclosure which is required to be of more than one-hour fire-resistive construction, the room or area shall have the same fire-resistive construction, including the same opening protection, as required for the adjacent exit enclosure.

7. [For SFM] An elevator lobby complying with Section 1114B.2.3.

1114B.2.2.2 [For SFM] Size. Each area for evacuation assistance shall provide at least two accessible areas that are not less than 30 inches by 48 inches (762 mm by 1219 mm). The area for evacuation assistance shall not encroach on any required exit width. The total number of such 30-inch by 48-inch (762 mm by 1219 mm) areas per story shall not be less than one for every 200 persons of calculated occupant load served by the area for evacuation assistance.

EXCEPTION: The building official may reduce the minimum number of 30-inch by 48-inch (762 mm by 1219 mm) areas to one for each area for evacuation assistance on floors where the occupant load is less than 200.

1114B.2.2.3 [For SFM] Adjacent stairway width. Each stairway adjacent to an area for evacuation assistance shall have a minimum clear width of 48 inches (1219 mm) between handrails.

1114B.2.2.4 [For SFM] Two-way communication.

1114B.2.2.4.1 [For SFM] A telephone with controlled access to a public telephone system or another method of two-way communication shall be provided between each area of refuge and the primary entry. The fire department may approve a location other than the primary entry.

1114B.2.2.4.2 [For DSA/AC] A method of two-way communication with both visible and audible communication shall be provided between each area of evacuation assistance and the primary entry. A button in the area of rescue assistance shall activate both a light in the area of rescue assistance indicating that rescue has been requested and a light at the primary entry indicating that rescue is being requested. A button at the primary entry shall activate both a light at the primary entry and a light in the area of rescue assistance indicating that the request has been received.

A telephone with controlled access to a public telephone system or another method of two-way communication shall be provided between each area of refuge and the primary entry. The fire department may approve a location other than the primary entry.

1114B.2.2.5 [For SFM] Identification. Each area for evacuation assistance shall be identified by a sign which states AREA FOR EVACUATION ASSISTANCE and the international symbol of accessibility. The sign shall be illuminated when exit sign illumination is required. In each area for evacuation assistance, instructions on the use of the area under emergency conditions shall be posted adjoining the two-way communication system.

1114B.2.3 [For SFM] Area for evacuation assistance, high- rise alternative. Within a building of any height or occupancy constructed in accordance with the requirements of Sections 403.1 through 403.10, an area for evacuation assistance may be located in the elevator lobby when:

1. The area for evacuation assistance complies with the requirements for size, two-way communication and identification as specified in Section 1114B.2.2; and

2. Elevator shafts and adjacent lobbies are pressurized as required for smoke-proof enclosures in Section 1005.3.3. Such pressurization system shall be activated by smoke detectors on each floor located in a manner approved by the building official. Pressurization equipment and its ductwork within the building shall be separated from other portions of the building by a minimum two- hour fire-resistive construction.

1114B.2.4 [For SFM] Alarms/emergency warning systems/accessibility. If emergency warning systems are required, they shall activate a means of warning the hearing impaired. Emergency warning systems as part of the fire-alarm system shall be designed and installed in accordance with NFPA 72 as amended in Chapter 35.


top