4.28 ALARMS
4.28.1 General
Alarm systems required to be accessible by 4.1
shall comply with 4.28. At a minimum, visual signal appliances
shall be provided in buildings and facilities in each of the following areas: restrooms and any other
general usage areas (e.g., meeting rooms), hallways,
lobbies, and any other area for common use.
4.28.2 Audible
Alarms
If provided, audible emergency alarms shall produce a sound that exceeds the prevailing
equivalent sound level in the room or space by at least 15 dbA or exceeds
any maximum sound level with a duration of 60 seconds by 5 dbA,
whichever is louder. Sound levels for alarm signals shall not exceed 120 dbA.
Note: Audible emergency signals must have an intensity and frequency that can attract
the attention of individuals who have partial hearing loss. People over 60 years of age
generally have difficulty perceiving frequencies higher than 10,000 Hz. An alarm signal
which has a periodic element to its signal, such as single stroke bells
(clang-pause-clang-pause), hi-low (up-down-up-down) and fast whoop (on-off-on-off) are
best. Avoid continuous or reverberating tones. Select a signal which has a sound
characterized by three or four clear tones without a great deal of "noise" in
between.
4.28.3 Visual Alarms
Visual alarm signal appliances shall be integrated into the building or facility alarm
system. If single station audible alarms are provided then single station visual alarm
signals shall be provided. Visual alarm signals shall have the following minimum
photometric and location features:
- 4.28.3(1)
The lamp shall be a xenon strobe type or equivalent.
- 4.28.3(2)
The color shall be clear or nominal white (i.e., unfiltered or clear filtered white
light).
- 4.28.3(3)
The maximum pulse duration shall be two-tenths of one second (0.2 sec) with a maximum duty
cycle of 40 percent. The pulse duration is defined as the time interval between initial
and final points of 10 percent of maximum signal.
- 4.28.3(4)
The intensity shall be a minimum of 75 candela.
- 4.28.3(5)
The flash rate shall be a minimum of 1 Hz and a maximum of 3 Hz.
- 4.28.3(6)
The appliance shall be placed 80 in (2030 mm) above the highest floor level within the
space or 6 in (152 mm) below the ceiling, whichever is lower.
- 4.28.3(7)
In general, no place in any room or space required to have a visual signal appliance shall
be more than 50 ft (15 m) from the signal (in the horizontal plane). In large rooms and
spaces exceeding 100 ft (30 m) across, without obstructions 6 ft (2 m) above the finish
floor, such as auditoriums, devices may be placed around the perimeter, spaced a maximum
100 ft (30 m) apart, in lieu of suspending appliances from the ceiling.
- 4.28.3(8)
No place in common corridors or hallways in which visual alarm signaling appliances are
required shall be more than 50 ft (15 m) from the signal.
Note: The specifications in this section do not preclude the use of zoned or coded
alarm systems.
4.28.4 Auxiliary Alarms
Units and sleeping accommodations shall have a visual alarm connected to the
building emergency alarm system or shall have a standard 110-volt
electrical receptacle into which such an alarm can be connected and a means by which a
signal from the building emergency alarm system can trigger such an auxiliary alarm. When
visual alarms are in place the signal shall be visible in all areas of the unit or room.
Instructions for use of the auxiliary alarm or receptacle shall be provided.
Note: Locating visual emergency alarms in rooms where persons who are deaf may work or
reside alone can ensure that they will always be warned when an emergency alarm is
activated. To be effective, such devices must be located and oriented so that they will
spread signals and reflections throughout a space or raise the overall light level
sharply. However, visual alarms alone are not necessarily the best means to alert
sleepers. A study conducted by Underwriters Laboratory (UL) concluded that a flashing
light more than seven times brighter was required (110 candela v. 15 candela, at the same
distance) to awaken sleepers as was needed to alert awake subjects in a normal daytime
illuminated room.
For hotel and other rooms where people are likely to be asleep, a signal-activated
vibrator placed between mattress and box spring or under a pillow was found by UL to be
much more effective in alerting sleepers. Many readily available devices are
sound-activated so that they could respond to an alarm clock, clock radio, wake-up
telephone call or room smoke detector. Activation by a building alarm system can either be
accomplished by a separate circuit activating an auditory alarm which would, in turn,
trigger the vibrator or by a signal transmitted through the ordinary 110-volt outlet.
Transmission of signals through the power line is relatively simple and is the basis of
common, inexpensive remote light control systems sold in many department and electronic
stores for home use. So-called "wireless" intercoms operate on the same
principal. |