Wet Vents              Wet Vents Sketch, Vertical Wet Vents Sketch

  1. Limited to trap arm of one and two unit fixtures. UPC 908.1.

  2. Min. 2" and one pipe size larger than the required waste. UPC 908.2. Vertical Wet Vents Sketch

  3. All wet-vented fixtures shall be on the same floor, and fixtures with continuous vents discharging into wet vents shall be on the same floor level as the wet vented fixtures. UPC 908.1.

  4. Wet vents shall not serve more than four fixtures. UPC 908.1.