|
Gas
Piping
Gas
piping sizing Table
Gas Sizing
Worksheet
- Metal
gas pipes buried in ground shall have minimum 12" cover
and be factory wrapped. UPC 1211.5.
- Plastic
gas pipes shall have min. 18" cover and shall also have
#18 AWG tracer attached. UPC 1211.16
- Gas
pipes shall not be directly embedded in concrete or underslabs.
UPC 1211.3.
Exception: When necessary due to structural conditions and
with prior Administrative Authority concurrence, approved type
gas piping may be installed under slabs (i.e. gas pipe in special
sleeves (conduits) or accessible trenches (channels). See sketch
for options.
- Gas
ferrous metals pipes shall be factory wrapped. 609.3.1.
- Gas
Testing: 10 psi. (6" of mercury) for 15 minutes. UPC 1204.3.2.
- Gas
piping material: Wrought iron, steel (galvanized or black) or
yellow brass. UPC 1210.1.
- Gas
piping shall be polyethylene pipe only for exterior-bury conditions.
UPC 1210.1.
- Buried
galvanized pipe shall have factory-wrap. UPC 1211.3.
- Exposed
gas piping shall be installed 6" above ground. UPC 1211.3.
- Gas
Connections: Shutoff valves shall be less than 3 ft. from the
appliance on supply side of union. UPC 1211.15.

- Gas
Piping Sizing Work Sheet per UPC, Table 12-3 & section 1217.
Go!
Drains
[Drains &
Vents Sizing Table]
1.
Materials:
-
Drainage
piping shall be cast iron, galvanized steel, galvanized
wrought iron, lead, copper, brass, Schedule 40 ABS DWV,
Schedule 40 PVC, DWV, extra strength vitrified clay pipe,
or other approved materials having a smooth and uniform
bore. UPC 701.1.
-
Slope
of Drains: 
-
Pipes
location with respect to footings. 
-
No
galvanized wrought iron or galvanized steel pipe to be used
underground and shall be kept at least 6" above ground.
UPC 701.1.1.
-
ABS
and PVC DWV piping installations shall be limited to structures
not exceeding three floors above grade. UPC 701.1.2.
In California:
DWV piping using ABS or PVC is limited to Two stories in
residential construction. State Plumbing Code, section 701.1.2.
-
Copper
tube for underground drainage and vent piping shall have
a weight of not less than that of copper drainage tube type
DWV. UPC 701.1.4. This means copper tubing types K, L &
M are acceptable.
-
Copper
Tubing Types Comparison Table: Click
here!
-
Copper
tube for above ground drainage and vent piping shall have
a weight of not less than that of copper drainage tube type
DWV. UPC 701.1.5.
-
Drainage
fittings shall be of cast iron, malleable iron, lead, brass,
clay, or other copper, ABS, PVC, vitrified approved materials
having a interior waterway smooth of the same diameter as
the piping served and all such fittings shall be compatible
with the type of pipe used. UPC 701.2.
-
Example
clickable DWV sketch!
- Traps:
Designed to provide a liquid seal which will prevent back passage
of sewer gas.
- Traps
and arms shall be of the same size. UPC 1003.3.
- Traps
Max. Fixture Unit Loading:

- Drain
Pipes Sizing Table based on F.U. served:

- Fixtures
Unit (F.U.), Traps & Trap Arms:

- Drainage
& Venting Systems shall be tested with a 10-ft. head of
water.
- Floor
drains subject to infrequent use require automatic trap primer
devices that are accessible for maintenance. UPC 1007.0.
- Indirect
Waste Piping:

- Island
Sink Special Venting, UPC 909.0:

- No fitting, fixture
& piping connection , device or method of installation which
obstructs or retards the normal flow of water, waste, sewage
or air in a drainage or venting system, shall be used.
- Pipe trenches installation
guidelines:

- Location:
Shall be accessible. UPC 707.9.
- Required
at upper terminal of horizontal runs. UPC 707.4.
- Required
at each 100 ft. of run. UPC 707.
- Required
for each 135° of direction change. UPC 707.6.
- Cleanout
required at junction between building drain and building sewer.
- Cleanouts are not
required on horizontal piping above the first floor.
- Underfloor
piping should extend above floor or outside building when access
is less than 18" vertical or 30" horizontal. UPC 707.10.
- Cleanouts
Sizing: Go!
Vents
- General:
Vent Pipes protect plumbing fixture traps against siphonage
and back-pressure. UPC, 901.0.
- Materials,
UPC 903.0:
- Cast
iron, galvanized steel, galvanized wrought iron, lead, copper
brass, Schedule 40 ABS DWV, Schedule 40 PVC DWV or other approved
material.
- ABS
& PVC DWV piping limited to 3 stories.
In
California: DWV piping using ABS or PVC is limited to Two
stories in residential construction. State Plumbing Code,
section 701.1.2.
- Vents
Termination, UPC 906:

- Through
vent flashing & min. 6" above the roof.
- From
any Vertical Surface: 12" min.
- From
windows, doors, building openings & air intake or vent
shafts: 10 ft.
- From
Property Lines, except alleys & streets: 3 ft.
- For
Type "B" and "L" vents termination:

- Vent
Pipes sizing depends on its length and F.U. connected thereto,
UPC 904.0.

- The
total vent(s) area is required to be equal or more than the
area of the main building drain line.
Go to circle area & circumference table.
- Example
showing Vents Sizing- Go!
- Vents shall rise
a min. 6" above the Flood Level Rim of the plumbing fixture.

- Vent opening shall
not be below the trap weir of the plumbing fixture.
- Traps
serving sinks which are a part of the equipment of bars, soda
fountains and counters need not be vented. UPC 902.2.
Wet
Vents ,

- Limited
to trap arm of one and two unit fixtures. UPC 908.1.
- Min.
2" and one pipe size larger than the required waste. UPC
908.2.

- All
wet-vented fixtures shall be on the same floor, and fixtures
with continuous vents discharging into wet vents shall be on
the same floor level as the wet vented fixtures. UPC 908.1.
- Wet
vents shall not serve more than four fixtures. UPC 908.1.
- See
sketch!
Exhaust
Fans
- Backdraft
damper required at all exhaust fans. UMC 504.1.
- Keep
fans min. 3 ft. from building openings and property lines. UMC
504.4.
|